日期:2014-05-17  浏览次数:21542 次

关于三菱PLC内部编程地址的计算,会的来帮忙看下,是怎么计算得出的
数值:1194 04

1194表示D202这个地址的16进制,

04表示D202,D203为4个BYTE,

1194=(202*2)+4096的16进制数,

至于用它表示D202的起始位置,三菱故意要这么麻烦了.

++++++++++++++++++++++++++

以下引用网上找来的资料!
============================
由于没有寄存器类型信息,所以地址的计算十分关键,如D100和M100分别对应哪个地址呢?下面就是三菱Fx系列PLC地址对应表:

Public Const PLC_D_Base_AddRess = 4096  
Public Const PLC_D_Special_Base_AddRess = 3584
Public Const PLC_Y_Group_Base_AddRess = 160
Public Const PLC_PY_Group_Base_AddRess = 672
Public Const PLC_T_Group_Base_AddRess = 192
Public Const PLC_OT_Group_Base_AddRess = 704
Public Const PLC_RT_Group_Base_AddRess = 1216
Public Const PLC_M_SINGLE_Base_AddRess = 2048(命令为7或8时)
Public Const PLC_M_Group_Base_AddRess = 256
Public Const PLC_PM_Group_Base_AddRess = 768
Public Const PLC_S_Group_Base_AddRess = 0
Public Const PLC_X_Group_Base_AddRess = 128
Public Const PLC_C_Group_Base_AddRess = 448
Public Const PLC_OC_Group_Base_AddRess = 960
Public Const PLC_RC_Group_Base_AddRess = 1472
Public Const PLC_TV_Group_Base_AddRess = 2048
Public Const PLC_CV16_Group_Base_AddRess = 2560
Public Const PLC_CV32_Group_Base_AddRess = 3072 

当我们用DEVICE READ命令时,D100地址=100*2+4096;M100地址=100+256;不同的是D类型寄存器存放的是字,M寄存器存放的是位,同样是读两个字节,D100返回的就是PLC中D100地址的值,M类型寄存器返回的是M100到M116的值。所以当我们用FORCE ON 命令时,M100寄存器地址=100+2048;

这也没有什么复杂的,不是吗?可是三菱公司好像不甘于如此,FORCE ON/Off命令中地址排列与DEVICE READ/WRITE不同,是低位在前高位在后。如Y20,地址是0510H,代码中4个字节地址表示为:1005。(注意:Y寄存器为八进制,如Y20 地址=16+1280=0510H) 

===============================================

没有看懂 

1194=(202*2)+4096的16进制数,

是怎样计算得出的!

------解决方案--------------------
(202*2)+4096=4500转成16进制就等于1194H